E6: Communication Failure Within the System.
E6 TROUBLESHOOTING STEPS:
NOTES
-
If the E6 is displayed at power up then it is most likely an INDOOR unit issue.
-
If the E6 appears after 3 - 4 minutes then it is most likely an OUTDOOR unit issue.
-
E6 error codes will not reset until the problem is resolved.
-
Cool or Heat mode does not affect troubleshooting steps.
SAFETY NOTE: Use caution and remove the main power from the system when connecting or disconnecting any wires or plugs.
STEP 1: Verify the following
-
Color code of the 1, 2, 3, and Ground connections at indoor & outdoor units match.
-
Interconnecting cable is 14/4 600V stranded copper wire.
-
Properly connected earth ground from the outdoor unit to the electric panel.
-
Ensure solderless crimp connections are crimped correctly.
-
Check that the communication wire is not broken or spliced between indoor and outdoor units.
TIPS:
-
Interconnecting cable should have voltage and gauge rating on the outer casing.
-
Take pictures of the indoor and outdoor wiring to verify connections.
-
Write down on a notepad to confirm the connections.
STEP 2: Condensate pump or indoor service disconnect
-
With power off, verify condensate float breaks Terminal 3 to the indoor unit and make sure the float is closed.
-
Indoor service disconnect should be 3 pole.
-
Ensure the color code is correct through the disconnect.
-
Double-check for aftermarket accessories wired into the system (e.g., condensate pump, door switch, smoke detector, wet switch).
TIPS:
-
Condensate pumps might be behind the indoor wall mount with different-colored wires at the indoor unit terminal.
STEP 3: Keep all wires connected – measure & record voltage on a notepad
-
For a 230V unit:
-
N1 and 2 should read 0VDC-55VDC (fluctuating).
-
N1 and 3 should be 208/230VAC.
-
2 and 3 should be 208/230VAC.
-
N1 and G should be 115VAC.
-
2 and G should be 0-55VDC (fluctuating).
-
3 and G should be 115VAC.
-
-
For a 115V unit:
-
N1 to 2 should be 0VDC - 55VDC (fluctuating).
-
N1 and 3 should be 115VAC.
-
N1 and G should be 0VAC.
-
2 and G should be 0VDC-55VDC (fluctuating).
-
3 and G should be 115VAC.
-
TIPS:
-
Keep the black (-) meter lead on N1 except when reading from 2 to Ground.
STEP 4: Measure and record voltage at outdoor & indoor Unit (208/230V or 115V Unit)
-
Outdoor Unit:
-
Remove #2 wire.
-
N1 to 2 should read 54 to 56 VDC.
-
2 to G should read 54 to 56 VDC.
-
Reconnect #2 wire and move inside.
-
-
Indoor Unit:
-
Remove #2 wire from Terminal 2.
-
N1 and 2 wire should be 54 to 56 VDC.
-
2 Wire and G should be 54 to 56 VDC.
-
STEP 5: Check Ohm Interconnecting cable between indoor and outdoor unit
-
Turn off Main Power or Disconnect.
-
Remove wires 1, 2, 3, and G at indoor and outdoor units.
-
Ensure wires are separated and not touching metal.
-
Confirm there is no measurable resistance between any of the wires.
-
Tie all 4 wires together inside and recheck ohms resistance reading between outdoor unit wires - should be close to zero between all wires.
TIPS:
-
Ohm testing interconnecting wire may not always verify cable integrity under high voltage.
IF WRONG WIRE TYPE / WIRE SPLICED, OR UNIT IS NOT PROPERLY GROUNDED...
-
Replace Wire / Properly ground unit
TIPS:
-
Consider running a temporary interconnecting wire to test if it resolves the E6 error code.
IF CONDENSATE PUMP OR INDOOR SERVICE DISCONNECT ARE WIRED INCORRECTLY OR A/C VOLTAGE IS INCORRECT
-
Correct Wiring / Correct Power Supply
OUTDOOR UNIT: IF THE 54 TO 56VDC IS NOT PRESENT, IS BELOW 50VDC OR IS FLUCTUATING FROM N1 TO 2, WITH THE WIRE OFF #2 TERMINAL
-
Verify line voltage at the board, check fuses on the filter board, and/or main board for open circuits.
-
If fuses are closed circuit, power off and disconnect all DC components plugged into the board and recheck for the 54 to 56VDC.
-
If voltage is proper, a component could be the issue. Use an ohm meter to find a shorted or grounded component.
-
If voltage is still not proper, replacing the main board may solve the issue.
TIPS:
-
A grounded or shorted compressor, fan motor, EEV, or thermistors can cause an E6 error code.
INDOOR UNIT: WITH THE 2-WIRE DISCONNECTED INSIDE AND CONNECTED OUTSIDE AND THE VOLTAGE IS HIGHER THAN 56VDC FROM N1 TO THE 2-WIRE INSIDE
-
The interconnecting cable from inside to outside is faulty
TIPS:
-
Try a temporary interconnecting wire to see if it resolves the E6 error code / Verify the interconnecting cable is 14/4 600V stranded copper wire.
INDOOR UNIT: WITH THE 2-WIRE DISCONNECTED INSIDE AND CONNECTED OUTSIDE AND THE VOLTAGE IS HIGHER THAN 56VDC FROM N1 TO THE 2-WIRE INSIDE
-
Verify the indoor fan runs.
-
Switch mode to fan and turn on the fan. If the fan does not run, unplug it from the board and see if E6 is replaced with a new code for the indoor fan. If so, the fan motor may be faulty.
-
Ohm thermistors and check the display board if ok and the fan does run, then the indoor main board may be faulty.
TIPS:
-
A grounded or shorted fan motor, display board, or thermistors can drag down the communication bus voltage and cause an E6 error code.